315-4ne12 cpu 315sn gebruikte speed 7 PLC van Vipa

Vipa speed 7 gebruikte plc van het type 315-4ne12 cpu 315sn

Vipa speed 7 gebruikte plc van het type 315-4ne12 cpu 315sn

Type CPU 315SN/NET General information Note - Features SPEED7 technology 1 MB work memory Memory extension (max. 2 MB) PROFIBUS-DP master / PtP (switchable) CP 343 integrated SPEED-Bus - Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation) 270 mA Current consumption (rated value) 1 A Inrush current 5 A I²t 0.5 A²s Max. current drain at backplane bus 2.5 A Power loss 8.5 W Load and working memory Load memory, integrated 2 MB Load memory, maximum 2 MB Work memory, integrated 1 MB Work memory, maximal 2 MB Memory divided in 50% program / 50% data Memory card slot MMC-Card with max. 1 GB Hardware configuration Racks, max. 4 Modules per rack, max. 8 in multiple-, 32 in a single-rack configuration Number of integrated DP master 1 Number of DP master via CP 4 Operable function modules 8 Operable communication modules PtP 8 Operable communication modules LAN 8 Command processing times Bit instructions, min. 0.01 µs Word instruction, min. 0.01 µs Double integer arithmetic, min. 0.01 µs Floating-point arithmetic, min. 0.06 µs
Number of S7 counters 512 S7 counter remanence adjustable 0 up to 512 S7 counter remanence adjustable C0 .. C7 Number of S7 times 512 S7 times remanence adjustable 0 up to 512 S7 times remanence adjustable not retentive Data range and retentive characteristic Number of flags 8192 Byte Bit memories retentive characteristic adjustable adjustable 0 up to 8192 Bit memories retentive characteristic preset MB0 .. MB15 Number of data blocks 4095 Max. data blocks size 64 KB Number range DBs 1 ... 4095 Max. local data size per execution level 510 Byte Max. local data size per block 510 Byte Blocks Number of OBs 24 Maximum OB size 64 KB Total number DBs, FBs, FCs - Number of FBs 2048 Maximum FB size 64 KB Number range FBs 0 ... 2047 Number of FCs 2048 Maximum FC size 64 KB Number range FCs 0 ... 2047 Maximum nesting depth per priority class 8 Maximum nesting depth additional within an error OB 4 Time Real-time clock buffered Clock buffered period (min.) 6 w Type of buffering Vanadium Rechargeable Lithium Battery Load time for 50% buffering period 20 h Load time for 100% buffering period 48 h Accuracy (max. deviation per day) 10 s Number of operating hours counter 8 Clock synchronization Synchronization via MPI Master/Slave Synchronization via Ethernet (NTP) Slave Address areas (I/O) Input I/O address area 8192 Byte Output I/O address area 8192 Byte Process image adjustable Input process image preset 256 Byte
Output process image preset 256 Byte Input process image maximal 2048 Byte Output process image maximal 2048 Byte Digital inputs 65536 Digital outputs 65536 Digital inputs central 1024 Digital outputs central 1024 Integrated digital inputs - Integrated digital outputs - Analog inputs 4096 Analog outputs 4096 Analog inputs, central 256 Analog outputs, central 256 Integrated analog inputs - Integrated analog outputs - Communication functions PG/OP channel Global data communication Number of GD circuits, max. 8 Size of GD packets, max. 54 Byte S7 basic communication S7 basic communication, user data per job 76 Byte S7 communication S7 communication as server S7 communication as client - S7 communication, user data per job 160 Byte Number of connections, max. 32 Functionality Sub-D interfaces Type X2 Type of interface RS485 Connector Sub-D, 9-pin, female Electrically isolated MPI MP²I (MPI/RS232) - DP master - DP slave - Point-to-point interface - Type X3 Type of interface RS485 Connector Sub-D, 9-pin, female Electrically isolated MPI - MP²I (MPI/RS232)

DP master yes DP slave yes Point-to-point interface Functionality MPI Number of connections, max. 32 PG/OP channel Routing Global data communication S7 basic communication S7 communication S7 communication as server S7 communication as client - Transmission speed, min. 19.2 kbit/s Transmission speed, max. 12 Mbit/s Functionality PROFIBUS master PG/OP channel Routing S7 basic communication S7 communication S7 communication as server S7 communication as client - Activation/deactivation of DP slaves Direct data exchange (slave-to-slave communication) - DPV1 Transmission speed, min. 9.6 kbit/s Transmission speed, max. 12 Mbit/s Number of DP slaves, max. 124 Address range inputs, max. 8 KB Address range outputs, max. 8 KB User data inputs per slave, max. 244 Byte User data outputs per slave, max. 244 Byte Functionality PROFIBUS slave PG/OP channel Routing S7 communication S7 communication as server S7 communication as client - Direct data exchange (slave-to-slave communication) - DPV1 Transmission speed, min. 9.6 kbit/s Transmission speed, max. 12 Mbit/s Automatic detection of transmission speed Transfer memory inputs, max. 244 Byte Transfer memory outputs, max. 244 Byte Address areas, max. 32 User data per address area, max. 32 Byte Point-to-point communication PtP communication Interface isolated RS232 interface - RS422 interface - RS485 interface Connector Sub-D, 9-pin, female Transmission speed, min. 150 bit/s Transmission speed, max. 115.5 kbit/s Cable length, max. 500 m Point-to-point protocol ASCII protocol STX/ETX protocol 3964(R) protocol RK512 protocol - USS master protocol Modbus master protocol Modbus slave protocol - Special protocols - Functionality RJ45 interfaces Type X5 Type of interface Ethernet 10/100 MBit Connector RJ45 Electrically isolated PG/OP channel Number of connections, max. 4 Productive connections - Type X8 Type of interface Ethernet 10/100 MBit Connector RJ45 Electrically isolated PG/OP channel Number of connections, max. 32 Productive connections Ethernet communication CP Number of productive connections, max. 8 Number of productive connections by Siemens NetPro, max. 8 S7 connections BSEND, BRCV, GET, PUT, Connection of active and passive data handling User data per S7 connection, max. 32 KB TCP-connections SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling User data per TCP connection, max. 64 KB ISO-connections SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling User data per ISO connection, max. 8 KB ISO on TCP connections (RFC 1006) SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling User data per ISO on TCP connection, max. 32 KB UDP-connections SEND and RECEIVE User data per UDP connection, max. 2 KB UDP-multicast-connections SEND and RECEIVE (max. 8 Multicast groups) UDP-broadcast-connections SEND Ethernet open communication Number of connections, max. 8 User data per ISO on TCP connection, max. 8 KB User data per native TCP connection, max. 8 KB User data per ad hoc TCP connection, max. 1460 Byte User data per UDP connection, max. 1472 Byte Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions (WxHxD) 80 mm x 125 mm x 120 mm Weight 430 g Environmental conditions Operating temperature 0 °C to 60 °C Storage temperature -25 °C to 70 °C Certifications UL508 certification yes