STEP1AC/24DC1,7 Phoenix Contact dinrail voeding 1,75A 24 volt DC.

STEP1AC/24DC1,7 Phoenix Contact dinrail voeding 1,75A 24 volt DC. Breed 54mm hoogte 90mm en diep 61mm.

 

Input data

Nominal input voltage 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 95 V DC ... 250 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Current consumption Approx. 0.6 A (120 V AC)
Current consumption Approx. 0.3 A (230 V AC)
Inrush surge current < 15 A (typical)
Power failure bypass > 25 ms (120 V AC)
Power failure bypass > 150 ms (230 V AC)
Input fuse 3.15 A (slow-blow, internal)
Permissible backup fuse B6
Permissible backup fuse B10
Permissible backup fuse B16
Type of protection Transient surge protection
Protective circuit/component

Varistor

Output data

Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 1.75 A (-25°C ... 55°C)
Output current 1.9 A (-25 °C ... 40 °C permanent)
Output current 3.75 A (maximum output current)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Control deviation < 1 % (change in load, static 10% ... 90%)
Control deviation < 2 % (change in load, dynamic 10% ... 90%)
Control deviation < 0.1 % (change in input voltage ±10%)
Residual ripple < 60 mVPP (20 MHz)
Peak switching voltages nominal load < 40 mVPP (20 MHz)
Maximum power dissipation NO-Load < 0.7 W
Power loss nominal load max. 5 W

General data

Width 54 mm
Height 90 mm
Depth 61 mm
Net weight 0.2 kg
Operating voltage display Green LED
Efficiency > 89 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 3.75 kV AC (routine test)
Degree of protection IP20
Protection class II
MTBF (IEC 61709, SN 29500) > 500000 h (IEC 61709)
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: horizontal 0 cm, vertical 3 cm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers IEC 61558-2-17
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Shipbuilding approval Germanischer Lloyd (EMC 1), ABS, NK
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safe isolation DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment DIN VDE 0106-101
Standard – Limitation of mains harmonic currents EN 61000-3-2
Certificate CB Scheme
UL approvals UL/C-UL listed UL 508
UL approvals UL/C-UL Recognized UL 60950
UL approvals NEC Class 2 as per UL 1310
UL approvals UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
Surge voltage category III

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Stripping length 6.5 mm
Screw thread

M3

 

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Stripping length 6.5 mm