MINI-PS100-240AC2X15DC1 Phoenix mini power voeding 2938743.

MINI-PS100-240AC2X15DC1 Phoenix mini power voeding 2938743 Primair 100-240VAC secundair 2x15VDC 1 Amp 45MM

Input data

Nominal input voltage 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 90 V DC ... 350 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Current consumption Approx. 0.6 A (120 V AC)
Current consumption Approx. 0.4 A (230 V AC)
Current consumption Approx. 0.8 A (90 V DC)
Current consumption Approx. 0.3 A (350 V DC)
Nominal power consumption 15 W
Inrush surge current < 35 A (typical)
Power failure bypass > 30 ms (120 V AC)
Power failure bypass > 150 ms (230 V AC)
Input fuse 2.5 A (slow-blow, internal)
Permissible backup fuse 6 A
Permissible backup fuse 10 A
Permissible backup fuse 16 A
Additional text characteristic B

Output data

Nominal output voltage ± 15 V DC ±1%
Output current 2x 1 A (-25 °C ... 60 °C)
Output current 2x 1.5 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for assembling redundant systems and increasing efficiency
Connection in series Yes
Current limitation Approx 4.4 A (in the event of a short circuit)
Control deviation < 2 % (change in load, static 10% ... 90%)
Control deviation < 3 % (change in load, dynamic 10% ... 90%)
Control deviation < 0.1 % (change in input voltage ±10%)
Residual ripple < 30 mVPP (20 MHz)
Peak switching voltages nominal load < 20 mVPP (20 MHz)
Maximum power dissipation NO-Load 2 W
Power loss nominal load max. 8 W

General data

Width 45 mm
Height 99 mm
Depth 107 mm
Net weight 0.25 kg
Operating voltage display Green LED
Efficiency > 80 % (for 230 V AC and nominal values)
Insulation voltage input/output 3 kV (routine test)
Insulation voltage input/output 4 kV (type test)
Degree of protection IP20
Protection class II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500) > 500000 h
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 50081-2
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safe isolation DIN VDE 0106-1010
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Equipment safety GS (tested safety)
UL approvals UL/C-UL listed UL 508
UL approvals UL/C-UL Recognized UL 60950
UL approvals UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D